Fire-Lite MS-2 (2-Zone 24VDC) Fire Alarm Control Panel
For those looking to install a complete Fire Alarm System,
we have all of the compatible components necessary such as:
* and much more. Please inquire!
The Fire Lite MS-2 and MS-2E Fire Alarm Control Panels bring the latest in microprocessor technology to conventional fire controls. The MS-2 is compatible with the new i smoke detectors from System Sensor, and provides such advanced features as drift compensation, maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices is provided, using three selections for manufacturer protocol. The NAC protocol includes the ability to silence audible devices while strobes continue to flash, using only a single pair of wires. The MS-2 also is compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. For 240 VAC operation, order MS-2E. See the Fire Lite Device Compatibility Document 15384 for a complete list of compatible devices.
NOTE: Unless indicated otherwise, the term MS-2 refers to both MS-2 and MS-2E models.
Two Style B (Class B) IDCs (Initiating Device Circuits).
One Style Y (Class B) NAC (Notification Appliance Circuit).
Drift compensation automatically adjusts detector sensitivity
and increases resistance to false alarms caused
Maintenance Alert LEDs (per zone) warn of excessive
dirt accumulation, preventing false alarms (meets
Detector sensitivity is automatically measured by the
detector, which automatically adjusts its sensitivity back
to the factory settings when it becomes more sensitive
due to contaminants settling in the chamber.
Wireless handheld sensitivity meter eliminates the
need for voltmeters, magnets and a physical connection
to the detector. The reader displays sensitivity in
Supervisory LED (per zone) provides warning if a detector
senses temperature approaching freezing.
Special test protocol and LED indication allows quick
test of all detectors without need for a ladder.
NAC synchronization features:
Provides synchronization of standard ANSI audible signals
Provides synchronization of ADA compliant strobes
Selectable for System Sensor, Wheelock and Gentex
Selective Silence feature allows manual silence of
horns while strobes continue to flash on the same NAC.
Silent or Audible Walk Test operation mode commanded
from the front keypad, with automatic return to normal after
Alarm verification selectable per zone.
Each zone may be programmed for supervisory or fire,
with separate red and yellow LEDs.
Disable switches provided per zone.
Selective Silence (horn-strobe mute)
Silenceable or Nonsilenceable
Form-C Alarm and Trouble relays.
3.0 amps total usable current.
Optional dress panel (P/N DP-MS2/4).
Zone Enable/Disable (one per zone)
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Piezo sounder for alarm, trouble, supervisory and maintenance.
Activation of a compatible smoke detector or any normallyopen
fire alarm initiating device activates audible and visual
signaling devices, illuminates an indicating LED, sounds
the piezo sounder at the FACP, activates the FACP alarm
relay and operates an optional module used to notify a
remote station or initiate an auxiliary control function.
MS-2: 120 VAC, 50/60 Hz, 2.3 A
MS-2E: 240 VAC, 50 Hz, 1.15 A.
Wire size: minimum 14 AWG (2.0 mm ) with 600 V insulation.
Battery (sealed lead-acid only) J8
Maximum charging circuit: normal flat charge 27.6 VDC
Maximum battery charger capacity: 18.0 AH battery (two
7.0 AH batteries can be housed in the FACP cabinet.
Larger batteries require a separate battery box such as
Initiating Device Circuits TB3
Operation: all zones Style B (Class B).
Normal operating voltage: nominal 22 VDC.
Alarm current: 15 mA minimum.
Short-circuit current: 40 mA maximum.
Maximum loop resistance: 100 ohms.
End-of-line resistor: 4.7K ohm, 1/2 watt (P/N 71252).
Compatible devices: Refer to Fire Lite Device Compatibility
Document 15384 for listed compatible devices.
Notification Appliance Circuits TB2
Normal operating voltage: nominal 24 VDC.
Maximum signaling current: 2.5 A total with standard transform.
Trouble Relay TB5 (fail-safe).
Relay contact ratings: 2.0 A @ 30 VAC (resistive).
Operating voltage: nominal 24 VDC.
Maximum available current: 500 mA appropriate for
powering four-wire smoke detectors (see notes below).
NOTES: 1) See the Fire Lite Device Compatibility Document
15384 for listed compatible devices. 2) Total current
for resettable power and one NAC must not exceed 3.0 A
Door: 15.342" (38.97 cm) high x 14.677" (37.28 cm) wide x
0.375" (0.95 cm) deep. Backbox: 15.0" (38.10 cm) high x
14.5" (36.83 cm) wide x 3.0" (7.62 cm) deep.
The cabinet can be surface mounted. The door is removable
during installation by opening and lifting it off the hinges.
The cabinet mounts using two key slots at the top of the
backbox and two additional 0.250" diameter holes at the
MS-2 Two-zone conventional FACP; 120 VAC, 50/60
MS-2E Same as above with 240 VAC, 50 Hz, 1.15 A
BB-17F Battery box, required to house two batteries
greater than 7 AH to a maximum of 18 AH.
MS-2RB MS-2(E) replacement board.
ALSO AVAILABLE: FM-200 EQUIPMENT
FM-200 Fire Suppression Systems Components, Engineering. We are CHEMETRON Fire Systems Representatives and will furnish equipment, design and engineer a system based upon the information provided to us. Please feel free to inquire at (***) 265-9347 or Email to FYRECOM@ROCHESTER.RR.COM.
Please disregard email address: Melinda.ruiz@chicagopartsnetwork.com, as that is no longer the email address used. The new email address is: Melinda.ruiz@chicagopartsnetwork.com. Thank
(Fire•lite ms-2 fire alarm control panel - 2 zonecontrol was posted and is owned by: Melinda Ruiz)
Contact: Melinda.ruiz@chicagopartsnetwork.com (Melinda Ruiz) (actual email hidden)
Contact Melinda.ruiz@chicagopartsnetwork.com (Melinda Ruiz) for more information.

Flag any violation to moderators committee

Your flagging message:




Fire•lite ms-2 fire alarm control panel - 2 zonecontrol